Heating
Please consult the table below for details on the sizing of our heating mats and their values:
| Width (m) | Length (m) | Area/m² | Watts/m² | Watts/Mat | Amps/Mat |
| 1.5 | 0.5 | 0.75 | 150 | 113 | 0.49 |
| 2.0 | 0.5 | 1.0 | 150 | 150 | 0.65 |
| 2.5 | 0.5 | 1.25 | 150 | 188 | 0.82 |
| 3.0 | 0.5 | 1.5 | 150 | 225 | 0.98 |
| 3.5 | 0.5 | 1.75 | 150 | 263 | 1.14 |
| 4.0 | 0.5 | 2.0 | 150 | 300 | 1.30 |
| 4.5 | 0.5 | 2.25 | 150 | 338 | 1.47 |
| 5.0 | 0.5 | 2.5 | 150 | 375 | 1.63 |
| 5.5 | 0.5 | 2.75 | 150 | 413 | 1.79 |
| 6.0 | 0.5 | 3.0 | 150 | 450 | 1.96 |
| 6.5 | 0.5 | 3.25 | 150 | 488 | 2.12 |
| 7.0 | 0.5 | 3.5 | 150 | 525 | 2.28 |
| 1.0 | 1.0 | 1.0 | 150 | 150 | 0.65 |
| 1.5 | 1.0 | 1.5 | 150 | 225 | 0.98 |
| 2.0 | 1.0 | 2.0 | 150 | 300 | 1.30 |
| 2.5 | 1.0 | 2.5 | 150 | 375 | 1.63 |
| 3.0 | 1.0 | 3.0 | 150 | 450 | 1.96 |
| 3.5 | 1.0 | 3.5 | 150 | 525 | 2.28 |
Primary Heat Source:
The Warmup® Underlaminate Heating Mats should cover at least 80% of the floor area of your room to be used as a primary heat source. The mats are available in various sizes, so choose a combination of mats that best enables you to cover the recommended 80% of your room. Plan the use of larger mats as much as possible and use smaller mats only as gap fillers.
Layout:
Before installing, draw an installation plan showing the placement of the mats, floor sensors, and junction box or boxes.

Warmup® Underlaminate Heaters are connected in parallel, usually through a junction box, to a Warmup® programmable thermostat.
NOTE: The mats are supplied with 5 metres of electrical cold tails. If this is not enough, ask your electrician to extend the electrical supply cables.
RCD:
When installing your Warmup® Underlaminate Heater please remember that an RCD needs to be fitted. Your RCD should meet one of the following standards:
- BS 4293
- IEC 61008
- IEC 61009
- IEC 60947-2
with 30mA maximum tripping current, and a response time of 0.2 seconds.